Illuminance and number-of-luminaires calculation (lumen method, EN 12464-1)

EN 12464-1 (2021) SIA 380/4 27 room types 4 layouts Dimensioned, to-scale SVG preview Shareable permalink

Room parameters

Hu = H − h determines k and UF.
UF — Utilization factor
MF — Environment
Layout
Real-time preview — automatic scaling
Number of luminaires
—luminaires
Indicative calculation

Sizing details

Preliminary lighting design in seconds

How many luminaires are needed for a 40 m² office? For a 60 m² classroom? For a 200 m² precision workshop? The lumen method, codified in the standard EN 12464-1 (indoor workplaces), gives the answer in a single formula: N = Em × A / (Φ × UF × MF). This tool applies the method in real time, lets you choose from 27 room types standardized, offers 4 architectural layouts typical values and draws a to-scale SVG layout to visualize the result immediately. Ideal for a quote, a preliminary design, a quick sketch check or as support for a client discussion.

The calculator does not replace a photometric simulation carried out in dedicated software for project validation (uniformity Uo, glare UGR, point calculations, inclined surfaces). It provides the estimated average illuminance Em and the power density in W/m² to compare with SIA 380/4, and a layout preview exportable as an image. To automate this work in AutoCAD with generation of the dimensioned layout plan and the luminaire schedule, see the command CALEP of the module ElectroCAD Tools.

How the lumen method works

The lumen method is the traditional procedure for preliminary sizing of indoor lighting, standardised since the 1960s and adopted as is in EN 12464-1 for the preliminary design. It is based on a simple energy balance: the total useful luminous flux on the working plane (Em × A in lumens) must equal the flux emitted by the luminaires (N × Φ) corrected by two combined factors, the utilisation factor UF (which models the optical losses between the luminaire and the working plane) and the maintenance factor MF (which models degradation over time).

Lumen method formula
N = (Em × A) / (Φ × UF × MF)
  • N : number of luminaires (to round up to the next integer and adapt to the layout)
  • Em : target average illuminance on the working plane, in lux (EN 12464-1 table)
  • A : room area, in m² (A = L × W)
  • Φ : nominal luminous flux of a luminaire, in lumens (manufacturer datasheet)
  • UF : utilization factor (unitless, 0.28 to 0.78)
  • MF : maintenance factor (unitless, 0.60 to 0.90)

The calculator also displays theroom index k = (L × W) / (Hu × (L + W)), where Hu = H − h is the useful mounting height. This index is the input to the manufacturers' UF tables: the larger k is, the better the room exploits the emitted flux (UF increases). A k of 1 characterizes a typical office room; below 0.6, the room is too tall or too narrow and the UF drops sharply, requiring more luminaires to compensate.

Em values by room type (EN 12464-1)

EN 12464-1 sets a minimum maintained illuminance on the working plane according to the visual task. Here are the main values built into the calculator dropdown, together with the UGR limit (discomfort glare) and the minimum colour rendering index Ra:

Room type / activityEm (lx)UGR maxRa min
Corridor, circulation area1002840
Dwelling, bedroom100—80
Dwelling, living room200—80
WC, changing room2002580
Meeting room3001980
School, classroom3001980
Children's classroom (kindergarten)3001980
Gymnasium3002260
Food store3002280
General office (data entry, reading)5001980
School, specialised classroom5001980
Reading, study5001980
Professional kitchen5002280
Office, technical drawing (CAD)7501680
Precision industrial workshop7501980
Medical practice, examination10001990
Operating room (general)10001990
High-precision industrial workshop15001680

For the exhaustive list (more than 250 entries), refer to the full text ofEN 12464-1 (2021 edition) or to the Em data sheets by usage category. The values above are task-area illuminances; the surrounding-area and background illuminances follow ratios of 0.5 to 0.75 depending on the context.

Choosing UF (utilisation factor) correctly

UF measures the share of the flux emitted by the luminaires that actually reaches the working plane, after reflections off the walls, ceiling and floor and after absorption by the room. It depends on four parameters: the photometric distribution of the luminaire (direct, indirect, direct/indirect, asymmetric), the reflectances ρp/ρm/ρs (ceiling/walls/floor, typically 0,7/0,5/0,2 for a light office, 0,5/0,3/0,1 for a dark workshop), the useful mounting height Hu = H − h and theroom index k. The manufacturer provides a UF table (k, ρp, ρm, ρs) for each luminaire.

Typical UF values for preliminary design, for a modern direct LED panel (LOR ≈ 1) with light reflectances 0.7/0.5/0.2: ≈0.49 in a narrow/tall room (k≈0.6); ≈0,62 in an ordinary office (k≈1) ; ≈0.78 in a wide, low room (k≈2); up to ≈0.92 for a large hall (k≈5). An indirect luminaire or one with a very closed diffuser goes considerably lower. The mode Auto (k) of the calculator looks up an 11-step table (k 0,6 → 5,0) aligned with manufacturer charts and the utilance values calculated by photometric simulation software. The mode Manual covers the 0,40-0,95 range for atypical cases. In the absence of a manufacturer datasheet, use 0,70 as the default for a normal commercial room with direct LED lighting.

Choosing MF (maintenance factor) correctly

MF incorporates four cumulative degradations between commissioning and the next maintenance intervention: LLMF (Lamp Lumen Maintenance Factor, luminous flux depreciation of the sources, typically 0,90 at 25 000 h for L80 LED), LSF (Lamp Survival Factor, failures before maintenance, negligible for modern LED), LMF (Luminaire Maintenance Factor, optical soiling of the luminaire, highly environment-dependent) and RSMF (Room Surfaces Maintenance Factor, degradation of the room surfaces). The calculator offers 3 discrete levels: Clean 0.80 (office, school, healthcare, annual cleaning); Normal 0.70 (clean workshop, light industry, retail, housing); Dirty 0.65 (dusty industry, foundry, agriculture, intensive kitchen).

The 4 available layouts

The calculator offers four layout patterns that cover 80 % of practical cases in residential and commercial buildings (the CALEP module of ElectroCAD Tools offers 30 for the final design, see our layout guide).

Regular grid (rows × cols)

Default pattern. Luminaires are placed on a regular grid with spacing dx in X and dy in Y. The wall distance is typically dx/2 and dy/2. Note: open-plan office, classroom, meeting room, laboratory. The calculator optimizes rows × cols to respect the room's L/W ratio, which makes dx ≈ dy and guarantees maximum uniformity with the simple lumen method. Empirical validity rule: spacing S ≤ 1.5 × Hu (otherwise the uniformity Uo drops below 0.6).

Staggered (odd rows offset)

Odd rows are offset by dx/2 relative to even ones. Advantage: better perceived visual uniformity (the eye no longer sees the grid), recommended in retail space, entrance hall, restaurant, reception area. With a staggered grid, dx can typically be increased by 10-15 % at equivalent uniformity Uo, i.e. saving 10 % of luminaires in large rooms.

Parallel lines

Continuous rows aligned with the long axis of the room. Indication: corridors, circulation halls, linear shops, workshops with aligned machines, garages, car parks, changing rooms. Advantage: consistency with the circulation axis and the orientation of workstations (the operator's shadow is cast behind them, never in front). For workshops, rows parallel to the main machine axis are the arrangement required by good industrial lighting practice.

Inner perimeter

Luminaires placed only along the four walls, at a constant distance from the edges. Indication: indirect lighting coves, wall-washing in retail and hospitality, rooms with a central technical ceiling (sprinkler, duct), exhibition halls. Estimated average Em lower at the centre of the room, to be supplemented by localized direct lighting or a ceiling downlight. An ambience and accent pattern, typically to be combined with a reduced downlight grid (« double layer » mode in CALEP).

Limitations of the lumen method

The lumen method gives theaverage illuminance Em on the working plane, i.e. the value integrated over the entire floor area of the room. It does not provide: uniformity Uo (ratio Em min / Em average, required ≥ 0.6 by EN 12464-1 in the task area), discomfort glare UGR (calculated by ray tracing from the observer's position), vertical illuminance Em,v on furniture fronts or faces, point illuminances (point by point), calculations on inclined surfaces (inclined CAD/drawing desks, tiered seating, stairs), or modelling of furniture that obstructs the flux.

Rule of good practice: lumen method for pre-design, quoting, preliminary design and sketch verification ; photometric simulation in dedicated software for final design validation, the dossier OIBT, the SIA 380/4 energy dossier and any binding tender.

Power density and SIA 380/4

SIA 380/4 (Swiss standard “Electrical energy in buildings”, 2017 revision) sets target and limit values for lighting power density in W/m², distinct from illuminance Em (which is an EN 12464-1 requirement, normative for comfort). Typical SIA 380/4 target limit values: 6 W/m² standard office, 8 W/m² school, 10 W/m² retail, 12 W/m² light industry. The calculator estimates the installed power from a reference LED efficacy of 110 lm/W (recent commercial LED). For a 500 lx office measuring 8×5 m, this typically gives 5-6 W/m², right on the SIA 380/4 target. Above 10 W/m² for an office, the design is non-compliant in energy terms and requires either more efficient luminaires (130-150 lm/W), a reduced Em, or a sensor-based flux dimming strategy (occupancy + daylight harvesting).

Automate luminaire layout in AutoCAD

This web tool covers preliminary design and costing. For the final design with automatic generation of the dimensioned layout plan, luminaire schedules and tender documents, the command CALEP d'ElectroCAD Tools applies the same EN 12464-1 methodology directly in AutoCAD: selection of room polygons (or import from the architect's plan), automatic application of Em per room type from the CRB CAN 2026 database, choice among 30 architectural layouts (see hexagonal and parallel-line algorithms), placement of luminaire DWG blocks with title block, material take-off for quotations and Excel/CSV export to the CAN service catalogue for the CRBX SIA 451 tender.

Discover ElectroCAD Tools CALEP module

Frequently asked questions

How do you calculate the number of luminaires for a room?

Apply the lumen method: N = (Em × A) / (Φ × UF × MF). Em is the target illuminance in lux according to EN 12464-1 (500 lx for an office), A the area in m², Φ the rated flux of one luminaire in lumens, UF the utilisation factor (0.5 to 0.7 typical) and MF the maintenance factor (0.7 to 0.8). N is then rounded up to the next whole number and distributed over a rectangular grid. Example with the calculator's assumptions: an 8×5 m office at 500 lx, Φ=4500 lm, automatic UF ≈0.78 (k≈1.7) and MF=0.80 (clean room) give N = (500×40)/(4500×0.78×0.80) ≈ 7.1, i.e. 8 luminaires in a 4×2 grid. With a mediocre luminaire entered in manual mode (UF=0.50, MF=0.70), the same room requires N ≈ 12.7, i.e. 13 luminaires.

What is the formula for lighting calculation?

The formula is N = (Em × A) / (Φ × UF × MF). It is used to pre-size the number of luminaires to achieve a target average illuminance Em. Em comes from the EN 12464-1 table, A is the area, Φ the rated flux, UF the utilisation factor (which depends on the reflectances and on the room index k = (L×W)/(Hu×(L+W))) and MF the maintenance factor. The formula estimates the average illuminance; it does not replace a photometric simulation for uniformity, UGR glare or point calculations.

How many lumens for an office?

EN 12464-1 requires 500 lx on the work surface for a general office. For a 20 m² office, the useful flux required is 500×20 = 10000 lm, i.e. ≈ 28600 lm nominal installed (UF=0.50, MF=0.70) or 6-7 LED panels of 4500 lm. For technical drawing, Em rises to 750 lx, i.e. about 50 % more luminaires.

Which maintenance factor to choose?

0,80 in offices/schools/healthcare (clean, annual cleaning); 0,70 in retail, housing, clean workshops, light industry; 0,65 in dusty industry, foundries, agriculture, intensive kitchens. MF includes LLMF (lamp depreciation), LSF (failures), LMF (luminaire soiling) and RSMF (surface degradation). For commercial pre-design, 0,70 by default (Normal mode of the calculator).

What height for the working plane?

0,75 to 0,85 m for offices and seated tasks; 0,90 m for school tables and standing workstations; 0,00 m for circulation areas and halls (floor plane); 1,00 m for standing industrial workshops. The useful mounting height Hu = H − h determines the room index k and the UF. For Em floor (corridor), h=0; for Em office, h=0,85.

Lumen method vs photometric simulation?

The lumen method gives the average illuminance Em in a few seconds, ideal for the preliminary design and the quotation. It does not provide uniformity Uo, UGR glare, point levels or calculations on inclined surfaces. A photometric simulation in dedicated software uses the manufacturer's IES/LDT files and calculates exact illuminances by ray tracing. Rule: lumen method for the preliminary design and quotation, simulation for validating the final design and the OIBT/SIA documentation.

This tool is provided for guidance for preliminary design and costing. It does not replace a professional photometric study (dedicated simulation software) required for validating the final design, the OIBT dossier and the SIA 380/4 energy dossier.