Three-phase current calculation

Rated current, inrush current depending on the starting method, minimum copper cross-section and C/D-curve circuit breaker rating — formula I = P/(√3·U·cosφ·η) compliant with NIBT 2020.

NIBT 2020 — SEV 1000:2020 IEC 60909 starting current Real-time calculation No registration required
Rated current Iₙ
14,97A

Detailed results

Direct-on-line starting Curve D circuit breaker

Indicative values. Check voltage drop and Kt/Kg factors per NIBT 5.2 before validation.

3N~ 5×2,5 mm² Cu Annotation câble — SIA 451 / IEC 60617
Notation to be carried over onto the single-line diagram.

Three-phase current formula and derivation of √3

In a balanced three-phase system, three sinusoidal voltages of equal amplitude are phase-shifted by 120° from one another. The voltage between a phase and neutral, called phase-to-neutral voltage V, is typically 230 V in Switzerland. The voltage between two phases, known as line-to-line voltage U, is 400 V. The ratio between these two voltages is not 2 but √3 ≈ 1,732, a direct consequence of the vector composition of two phases shifted by 120°: U = √3 · V.

The active power drawn by the three phases is P = 3 · V · I · cosφ, where I is the line current and cosφ the power factor. Replacing V by U/√3 yields the practical formula used by all designers: P = √3 · U · I · cosφ · η, i.e. I = P / (√3 · U · cosφ · η). If the apparent power S (in VA) is known, the formula simplifies to I = S / (√3 · U), with no cosφ involved since it is already included in S.

This formula applies to balanced three-phase loads: induction motors, transformers, 3~ heaters, rectifiers and inverters seen from the input side. For an unbalanced load (single-phase loads spread over the three phases), the current must be calculated phase by phase, taking into account the neutral current, which can reach up to √3 times the current of the most heavily loaded phase in the presence of harmonics (notably H3 from switch-mode power supplies).

Table of rated currents by motor power

Typical values at 400 V cosφ 0.85, efficiency η = 0.85 (IE2 asynchronous motor). For different conditions, use the calculator above.

PowerIₙ (A)Id direct-on-line (A)Id star-Δ (A)Cu cross-sectionCircuit breaker
0,55 kW1,16,52,71,5 mm²10 A — D
1,1 kW2,2135,51,5 mm²10 A — D
1,5 kW3,0187,51,5 mm²10 A — D
2,2 kW4,426111,5 mm²10 A — D
3 kW6,036151,5 mm²10 A — D
4 kW8,048201,5 mm²13 A — D
5,5 kW11,066271,5 mm²16 A — D
7,5 kW15,090372,5 mm²16 A — D
11 kW22,0132554 mm²25 A — D
15 kW30,0180756 mm²32 A — D
18,5 kW36,92229210 mm²40 A — D
22 kW43,926411010 mm²50 A — D
30 kW59,936015016 mm²63 A — D

Cross-sections selected for installation method B1 with a 25% margin between corrected Iz and Iₙ, in line with NIBT good practice. For buried or multi-core cables, or runs above 30 °C, apply the Kt and Kg factors of chapter 5.2 using our cable sizing calculator.

Star-delta starting: principle and limits

Starting star-delta is the traditional method for limiting the inrush current of three-phase squirrel-cage induction motors. The motor is designed to run in delta connection at the nominal supply voltage (each winding receives U_line). At start-up, it is temporarily switched to star connection (each winding receives U_line/√3 ≈ 0.577 · U): the voltage across the windings is divided by √3, the phase-to-phase current drawn is divided by 3, and consequently so is the line current. The torque, proportional to the square of the voltage, is also divided by 3.

In practice, we obtain Id ≈ 2.5 · Iₙ (versus 6 to 8 · Iₙ in direct-on-line) and a starting torque divided by 3 compared with the delta connection. This characteristic imposes two conditions of use: (1) the motor must have six accessible terminals on its terminal plate (U1/V1/W1 and U2/V2/W2) to allow switching, and (2) the driven machine must accept starting at reduced torque, i.e. unloaded or lightly loaded (fans, centrifugal pumps, unloaded compressors, band saws). Machines with high breakaway torque (crushers, loaded conveyors, piston compressors) cannot be started in star-delta.

The control diagram requires three contactors (line KL, star KS, delta KT) mechanically and electrically interlocked, plus a time delay of the star→delta changeover (typically 5 to 15 seconds depending on the load inertia). Since the 2000s, star-delta starting has largely been replaced by electronic soft starters (soft-starters) or by variable frequency drives, which offer a smoother, adjustable start compatible with all loads.

Phase balancing in three-phase systems

A three-phase system works best when the three phases L1, L2, L3 are evenly loaded. An imbalance generates a non-zero current in the neutral conductor, different voltage drops between phases, additional heating in transformers and, in the long run, a degradation of the voltage quality experienced by other consumers connected to the same transformer substation. The NIBT 4.7.3 recommends a maximum imbalance of 10 % between the most and least loaded phases.

On a residential or commercial distribution board, balancing is done when assigning phases to the single-phase circuit breakers. Practical method: list all single-phase feeders with their estimated power, sort them in descending order, and assign them alternately to L1/L2/L3 starting with the largest. Three-phase feeders (400 V cooking, heat pump, 11 kW EV charging station) are inherently balanced. CAD tools such as ElectroSchema automate this balancing transfer and flag imbalances above 10 % in real time.

ElectroCAD tools for the electrical designer

The three-phase current calculator completes the ElectroCAD tool ecosystem for pre-sizing and detailed design of Swiss electrical installations. See also the electrical power calculator (single/three-phase, watts/VA/var, cosφ ↔ tanφ conversion), the NIBT 2020 cable sizing calculator (voltage drop, Kt/Kg factors, installation methods B1/B2/C/E/F), our annotated example of a three-phase single-line diagram and the suite ElectroCAD Tools which integrates these calculations directly into AutoCAD via the EC_LIGNES command. All our calculations are based on the standard NIBT 2020 (SEV 1000:2020).

FAQ — Questions from designers

What is the three-phase current formula?

For a balanced three-phase load supplied at line-to-line voltage U, the line current is I = P / (√3 · U · cosφ · η) where P is in watts, U in volts, cosφ the power factor and η the efficiency. If the apparent power S in VA is known, the formula becomes I = S / (√3 · U). The factor √3 ≈ 1.732 comes from the relationship between line-to-line and line-to-neutral voltage in a balanced system. Example: 7.5 kW motor at 400 V, cosφ 0.85, η 0.85 → I = 7500 / (1.732 · 400 · 0.85 · 0.85) ≈ 14.97 A.

Why √3 in the three-phase formula?

In a balanced three-phase system, the voltage between two phases (line voltage) and the voltage between one phase and neutral (phase voltage) are related by U_line = √3 · U_phase, a geometric consequence of the 120° phase shift between the three phases. The total power drawn is P = 3 · U_phase · I · cosφ = √3 · U_line · I · cosφ. This is why the √3 factor appears as soon as the formula is expressed with the line voltage (400 V, 230 V industrial, 690 V), which is the voltage shown on a motor's rating plate.

What is the starting current of a three-phase motor?

On direct-on-line starting, a squirrel-cage induction motor typically draws Id = 6 to 8 · Iₙ for 0.5 to a few seconds, until the rotor reaches its rated speed. For a 7.5 kW 400 V motor with cosφ 0.85 and η 0.85, where Iₙ ≈ 15 A, you can therefore expect an Id of 90 to 120 A. With star-delta or soft-start starting, the current is divided by about 2.4: Id ≈ 2.5 · Iₙ, i.e. ~37 A, at the cost of an equally reduced starting torque.

What is the difference between curve C and curve D for a motor?

The C curve trips magnetically between 5 and 10 · Iₙ (general use: socket outlets, lighting, small loads). The D curve trips between 10 and 20 · Iₙ, designed to withstand the high starting peaks of direct-on-line induction motors, transformers and capacitor banks. For star-delta or soft starting, the C curve remains acceptable. For direct-on-line starting, the D curve avoids nuisance tripping. Also check selectivity with the upstream device.

How do you balance the phases in a three-phase system?

Balancing means distributing single-phase loads across the three phases L1/L2/L3. NIBT 4.7.3 recommends a maximum imbalance of 10 %. Practical method: add up the estimated power per circuit, sort into three columns, and distribute the heavy feeders first. On a schematic, indicate the connection phase at the foot of each single-phase circuit breaker. For balanced three-phase loads (motors, large 3~ heaters), no balancing calculation is required.

How do you annotate a three-phase cable on the diagram?

The cross bar of a three-phase cable carries the symbolic notation 3~ (three live conductors) or 3N~ (three phases + neutral), followed by the cross-section and the type. Example: 3N~ 5×6 mm² Cu means 5 conductors (L1, L2, L3, N, PE) of 6 mm² copper. For a motor without neutral, you write 3~ 4×4 mm² Cu. This convention appears in SIA 451 and IEC 60617. On the single-line diagram, a single line represents the whole cable, with an oblique stroke carrying the number of conductors and the cross-section.

Automate these calculations in AutoCAD?

ElectroSchema integrates three-phase sizing directly into the EC_LIGNES command: current, cross-section, breaker rating and 3N~ annotation generated in real time on the diagram.

Discover ElectroSchema Cable sizing calculation →