Three-phase current calculation
Rated current, inrush current depending on the starting method, minimum copper cross-section and C/D-curve circuit breaker rating — formula I = P/(√3·U·cosφ·η) compliant with NIBT 2020.
Three-phase current formula and derivation of √3
In a balanced three-phase system, three sinusoidal voltages of equal amplitude are phase-shifted by 120° from one another. The voltage between a phase and neutral, called phase-to-neutral voltage V, is typically 230 V in Switzerland. The voltage between two phases, known as line-to-line voltage U, is 400 V. The ratio between these two voltages is not 2 but √3 ≈ 1,732, a direct consequence of the vector composition of two phases shifted by 120°: U = √3 · V.
The active power drawn by the three phases is P = 3 · V · I · cosφ, where I is the line current and cosφ the power factor. Replacing V by U/√3 yields the practical formula used by all designers: P = √3 · U · I · cosφ · η, i.e. I = P / (√3 · U · cosφ · η). If the apparent power S (in VA) is known, the formula simplifies to I = S / (√3 · U), with no cosφ involved since it is already included in S.
Cette formule s'applique aux récepteurs triphasés équilibrés : moteurs asynchrones, transformateurs, chauffages 3~, redresseurs et onduleurs vus côté entrée. Pour un récepteur déséquilibré (charges monophasées réparties sur les trois phases), il faut calculer le courant phase par phase et tenir compte du courant dans le neutre, qui peut atteindre jusqu'à √3 fois le courant de la phase la plus chargée en présence d'harmoniques (notamment H3 des alimentations à découpage).
Table of rated currents by motor power
Typical values at 400 V cosφ 0.85, efficiency η = 0.85 (IE2 asynchronous motor). For different conditions, use the calculator above.
| Power | Iₙ (A) | Id direct-on-line (A) | Id star-Δ (A) | Cu cross-section | Circuit breaker |
|---|---|---|---|---|---|
| 0,55 kW | 1,1 | 6,5 | 2,7 | 1,5 mm² | 10 A — D |
| 1,1 kW | 2,2 | 13 | 5,5 | 1,5 mm² | 10 A — D |
| 1,5 kW | 3,0 | 18 | 7,5 | 1,5 mm² | 10 A — D |
| 2,2 kW | 4,4 | 26 | 11 | 1,5 mm² | 10 A — D |
| 3 kW | 6,0 | 36 | 15 | 1,5 mm² | 10 A — D |
| 4 kW | 8,0 | 48 | 20 | 1,5 mm² | 13 A — D |
| 5,5 kW | 11,0 | 66 | 27 | 1,5 mm² | 16 A — D |
| 7,5 kW | 15,0 | 90 | 37 | 2,5 mm² | 16 A — D |
| 11 kW | 22,0 | 132 | 55 | 4 mm² | 25 A — D |
| 15 kW | 30,0 | 180 | 75 | 6 mm² | 32 A — D |
| 18,5 kW | 36,9 | 222 | 92 | 10 mm² | 40 A — D |
| 22 kW | 43,9 | 264 | 110 | 10 mm² | 50 A — D |
| 30 kW | 59,9 | 360 | 150 | 16 mm² | 63 A — D |
Cross-sections selected for installation method B1 with a 25% margin between corrected Iz and Iₙ, in line with NIBT good practice. For buried or multi-core cables, or runs above 30 °C, apply the Kt and Kg factors of chapter 5.2 using our cable sizing calculator.
Star-delta starting: principle and limits
Starting star-delta est le procédé historique pour limiter le courant d'appel des moteurs asynchrones triphasés à cage. Le moteur est conçu pour fonctionner en couplage triangle sous la tension nominale du réseau (chaque enroulement reçoit U_composée). Au démarrage, on bascule temporairement en couplage étoile (chaque enroulement reçoit U_composée/√3 ≈ 0,577 · U) : la tension aux bornes des enroulements est divisée par √3, le courant absorbé phase-à-phase est divisé par 3, et par conséquent le courant de ligne aussi. Le couple, proportionnel au carré de la tension, est également divisé par 3.
In practice, we obtain Id ≈ 2.5 · Iₙ (versus 6 to 8 · Iₙ in direct-on-line) and a starting torque divided by 3 compared with the delta connection. This characteristic imposes two conditions of use: (1) the motor must have six accessible terminals on its terminal plate (U1/V1/W1 and U2/V2/W2) to allow switching, and (2) the driven machine must accept starting at reduced torque, i.e. unloaded or lightly loaded (fans, centrifugal pumps, unloaded compressors, band saws). Machines with high breakaway torque (crushers, loaded conveyors, piston compressors) cannot be started in star-delta.
The control diagram requires three contactors (line KL, star KS, delta KT) mechanically and electrically interlocked, plus a time delay of the star→delta changeover (typically 5 to 15 seconds depending on the load inertia). Since the 2000s, star-delta starting has largely been replaced by electronic soft starters (soft-starters) or by variable frequency drives, which offer a smoother, adjustable start compatible with all loads.
Phase balancing in three-phase systems
Un système triphasé fonctionne au mieux quand les trois phases L1, L2, L3 sont chargées de manière équilibrée. Un déséquilibre génère un courant non nul dans le conducteur de neutre, des chutes de tension différentes entre phases, des échauffements supplémentaires dans les transformateurs et, à terme, une dégradation de la qualité de tension perçue par les autres consommateurs raccordés au même poste de transformation. La NIBT 4.7.3 recommends a maximum imbalance of 10 % between the most and least loaded phases.
Sur un tableau résidentiel ou tertiaire, l'équilibrage se fait au moment de l'attribution des phases aux disjoncteurs monophasés. Méthode pratique : lister tous les départs monophasés avec leur puissance estimée, trier par ordre décroissant, et affecter en alternance L1/L2/L3 en partant des plus gros. Les départs triphasés (cuisson 400 V, PAC, borne VE 11 kW) sont nativement équilibrés. Les outils CAO comme ElectroSchema automate this balancing transfer and flag imbalances above 10 % in real time.
ElectroCAD tools for the electrical designer
The three-phase current calculator completes the ElectroCAD tool ecosystem for pre-sizing and detailed design of Swiss electrical installations. See also the electrical power calculator (single/three-phase, watts/VA/var, cosφ ↔ tanφ conversion), the NIBT 2020 cable sizing calculator (voltage drop, Kt/Kg factors, installation methods B1/B2/C/E/F), our annotated example of a three-phase single-line diagram and the suite ElectroCAD Tools which integrates these calculations directly into AutoCAD via the EC_LIGNES command. All our calculations are based on the standard NIBT 2020 (SEV 1000:2020).
FAQ — Questions from designers
What is the three-phase current formula?
For a balanced three-phase load supplied at line-to-line voltage U, the line current is I = P / (√3 · U · cosφ · η) where P is in watts, U in volts, cosφ the power factor and η the efficiency. If the apparent power S in VA is known, the formula becomes I = S / (√3 · U). The factor √3 ≈ 1.732 comes from the relationship between line-to-line and line-to-neutral voltage in a balanced system. Example: 7.5 kW motor at 400 V, cosφ 0.85, η 0.85 → I = 7500 / (1.732 · 400 · 0.85 · 0.85) ≈ 14.97 A.
Why √3 in the three-phase formula?
En triphasé équilibré, la tension entre deux phases (composée) et la tension entre une phase et le neutre (simple) sont liées par U_composée = √3 · U_simple, conséquence géométrique du déphasage de 120° entre les trois phases. La puissance totale absorbée vaut P = 3 · U_simple · I · cosφ = √3 · U_composée · I · cosφ. C'est pourquoi le facteur √3 apparaît dès qu'on exprime la formule avec la tension composée (400 V, 230 V industriel, 690 V), qui est la tension lue sur la plaque signalétique d'un moteur.
What is the starting current of a three-phase motor?
On direct-on-line starting, a squirrel-cage induction motor typically draws Id = 6 to 8 · Iₙ for 0.5 to a few seconds, until the rotor reaches its rated speed. For a 7.5 kW 400 V motor with cosφ 0.85 and η 0.85, where Iₙ ≈ 15 A, you can therefore expect an Id of 90 to 120 A. With star-delta or soft-start starting, the current is divided by about 2.4: Id ≈ 2.5 · Iₙ, i.e. ~37 A, at the cost of an equally reduced starting torque.
What is the difference between curve C and curve D for a motor?
La courbe C déclenche le magnétique entre 5 et 10 · Iₙ (usage général : prises, éclairage, petits récepteurs). La courbe D déclenche entre 10 et 20 · Iₙ, dimensionnée pour supporter les fortes pointes de démarrage des moteurs asynchrones en démarrage direct, des transformateurs et des batteries de condensateurs. Pour un démarrage étoile-triangle ou progressif, la courbe C reste acceptable. Pour un démarrage direct, la courbe D évite les déclenchements intempestifs. Vérifier aussi la sélectivité avec l'amont.
How do you balance the phases in a three-phase system?
L'équilibrage consiste à répartir les charges monophasées sur les trois phases L1/L2/L3. NIBT 4.7.3 recommande un déséquilibre maximum de 10 %. Méthode pratique : sommer la puissance estimée par circuit, trier en trois colonnes, et répartir les départs lourds en premier. Sur un schéma, indiquer la phase de raccordement en pied de chaque disjoncteur monophasé. Pour les récepteurs triphasés équilibrés (moteurs, gros chauffages 3~), aucun calcul d'équilibrage n'est nécessaire.
How do you annotate a three-phase cable on the diagram?
The cross bar of a three-phase cable carries the symbolic notation 3~ (three live conductors) or 3N~ (three phases + neutral), followed by the cross-section and the type. Example: 3N~ 5×6 mm² Cu means 5 conductors (L1, L2, L3, N, PE) of 6 mm² copper. For a motor without neutral, you write 3~ 4×4 mm² Cu. This convention appears in SIA 451 and IEC 60617. On the single-line diagram, a single line represents the whole cable, with an oblique stroke carrying the number of conductors and the cross-section.